Supply, 3c x 185mm 12kV (red) SWA cable
Quantity: 2,500 meters
ISO 9001 from Factory
Parameter Value
Site Elevation above MSL +550m
Design Barometric Pressure (masl) 1.013 bara (760 mmHg)
Site Ambient Temperature Maximum + 55 deg C
Site Ambient Temperature Minimum - 10 deg C
Site Ambient Temperature Design + 45 deg C
Black Body Temperature + 80 deg C
Ground Temperature @1.0 m depth + 10 deg C (Winter) / + 40 deg C (Design)
Relative Humidity (max) 92%
Relative Humidity (min) 18%
Relative Humidity (average) 33%
Atmospheric Conditions Occasional dust / sand storms
Earthquake: (Modified Mercalli Scale)
Design seismic zone
VI (Strong)
Design Life 20 years
Maintenance Interval (min) 2 years
Voltage supply ± 10%
Frequency ± 5%