Refer to your offer for the transformer, please find below our comment
- Submit compliance or deviation to the below requirements
A Specification : Requirement TIEPCO Compliance
1 Rated Power : 2,500KVA
2 Rated Primary voltage : 0.38KV (Star)
3 Rated Secondary voltage at No Load : 6.6KV (Delta)
4 Rated Frequency : 50Hz
5 Connection and Vector Group : Dyn11
6 Type of Oil sealing : Hermitically sealed
7 Tank Type : Corrugated Fins
8 Winding material (HV/LV) : Copper
9 Phase : 3
10 Cooling : ONAN ( Oil type )
11 Type of oil : Mineral Oil
12 Vector group : Dyn11
13 %Z : 6%
14 Cabe entry : Bottom
15 Tapping on MV Winding : +/- 2 x 2.5% 4 Steps (5 Positions)
16 Protection Degree : IP54 (Outdoor type)
17 LV Cable Termination Box : Required
18 MV Cable Termination Box : Required
19 Pressure Relief valve : Required
20 Oil level Indicator : Required
21 Oil temperature indicator : Required
22 DMCR (Detection Measurement Control Relay) : Required
23 Mount